To find the total duct leakage that s basically all you do.
Duct blaster total leakage test.
The duct blaster fan is first connected to the duct system at the air handler cabinet or a return grille.
The diagram above taken from the energy conservatory s duct blaster manual shows the setup for the total leakage test.
Duct air leakage test not required where ducts and air handlers are entirely within the building thermal envelope.
The only other thing you need to make sure you do is keep the spaces where the ducts are at the same pressure as the outdoors as much as you can anyway.
After temporarily sealing all remaining.
25 pa across the entire system including manufacturer s air handler enclosure all registers taped or otherwise sealed exception.
Duct leakage measurements are used to diagnose and demonstrate leakage problems estimate efficiency losses from duct leakage and certify the quality of duct system installation.
Total leakage measured with a pressure differential of 0 1 inch w g.
A duct blaster and a blower door.
According to energy star certified homes version 3 rev 08 for ducts in unconditioned spaces such as unconditioned vented attics or crawlspaces both tests should be conducted.
Duct blaster a duct blaster is used to directly pressure test the duct system for air leaks much the same way a plumber pressure tests water pipes for leaks.
The duct blaster fan is first connected to the duct system at the air handler cabinet or a return grille.