Irc 2015 n1103 3 4 allows the following duct leakage.
Duct leakage test results.
Building leakage and duct leakage test results should be recorded on each dwelling unit s energy certificate as required under section r401 3.
A duct leakage test duct testing can be performed at rough in before drywalling or post construction.
The system will need to achieve a leakage rate of less than 4 cfm cubic feet per minute per 100 square feet of the home.
Th e designer should carefully consider the following information in establishing allowable leakage speciļ¬ cations.
However our local utah code has a carve out allowing 7 cfm per 100 sq ft.
If the air handler is not yet installed we will test the supply and return sides of the system independently and add the 2 leakage totals together to determine the total leakage.
R101 4 3 1 mechanical systems when a space conditioning system is altered by the installation or replacement of space conditioning equipment including replacement of the air handler outdoor condensing unit of a split system air conditioner or heat pump cooling or heating coil or the furnace heat exchanger the duct system that is connected to the new or replacement space conditioning equipment.
Rough in test less than 4 cfm per 100 sq ft which for my house is about 160 cfm if the air handler is included in the leakage test.
The total amount of leakage in the system is determined by pressurizing or depressurizing the system with the duct blaster to 25 pascals which is equal to 0 1 inches of water column.
A duct leakage tester is a diagnostic tool designed to measure the airtightness of forced air heating ventilating and air conditioning ductwork.
Duct leakage test results existing construction washington state energy code reference.
Duct leakage test results rough in test air handler installed total leakage 6 cfm per 100 ft2 of conditioned floor area tested at a pressure differential 25pa 0 1 in w g across roughed in system all register boots taped or otherwise sealed.
Each cubic foot of air moved will carry with it 30 btu h.
It is table 4 1 on page 4 3 in the 1985 smacna hvac air duct leakage test manual and table 1 1 on page 1 11 in the 2005.
The combination of pressure and fan flow measurements are used to determine the ductwork airtightness.
If that system has a measured duct leakage of 10 100 cfm25 it is losing 3 000 btu h 1 4 ton of cooling to the outdoors.
An appropriate leakage rate that results in minimal leakage at minimal expense.
Does table 1 look familiar.
Sampling townhouse communities and multifamily properties with 10 or more dwelling units must request dcra s approval to utilize sampling.
The airtightness of ductwork is useful knowledge when trying to improve energy conservatio.
In both cases the requirements are the same.